Mechanical Limit Switch Module - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

1 fault message output
Binary output: Terminals 31 and 32
Connection
Signal state High
(not triggered)
Signal state Low (triggered)
Auxiliary power U
H
Connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
12.8.4

Mechanical limit switch module

Mechanical limit switch module
Limit encoder with mechanical
switching contacts
2 limit contacts
1 binary output: Terminals 41 and 42
2 binary output: Terminals 51 and 52
Max. switching current AC/DC
For connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
Max. switching voltage AC/DC
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Without Ex protection
At switching amplifier in accordance with EN 60947-5-6: (NAMUR), U
R = 1.1 kΩ
R = 10 kΩ
U
≤ DC 35 V
H
I ≤ 20 mA
-
-
-
The 3 outputs are galvanically isolated from the basic device.
Without Ex protection
6DR4004-8K
4 A
-
-
-
250 V/24 V
With Ex protection Ex "ia"
1 kΩ).
> 2.1 mA
< 1.2 mA
-
U
= DC 15 V
i
I
= 25 mA
i
P
= 64 mW
i
C
= 5.2 nF
i
L
= negligibly small
i
DC 840 V, 1 s
With Ex protection Ex ia
6DR4004-6K
-
U
= DC 30 V
i
I
= 100 mA
i
P
= 750 mW
i
C
= negligibly small
i
L
= negligibly small
i
DC 30 V
Technical data
12.8 Option modules
With Ex protection Ex "ic",
"nA", "t"
= 8.2 V, R
=
H
i
> 2.1 mA
< 1.2 mA
-
"ic":
U
= DC 15 V
i
I
= 25 mA
i
"nA":
U
≤ DC 15 V
n
P
≤ 64 mW
n
C
= 5.2 nF
i
L
= negligibly small
i
With Ex protection Ex "ic",
"nA", "t"
6DR4004-6K
-
"ic":
U
= 30 V DC
i
I
= 100 mA
i
"nA": Un ≤ 15 V DC
C
= negligibly small
i
L
= negligibly small
i
DC 30 V
253