Overview Of Error Codes - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Alarm, error, and system messages
10.3 Online diagnostics
10.3.2

Overview of error codes

Overview of error codes that activate the fault message output
Error
Three-
Event
code
stage
No
Actual-value re-
1
sponse has ex-
ceeded values for
TIM and LIM
No
Device not in "Au-
2
tomatic" mode
No
Binary input BIN1
3
or BIN2 active
Yes
Limit for number of
4
total strokes ex-
ceeded
Yes
Limit for number of
5
changes in direc-
tion exceeded
Yes
Lower endstop
6
limit exceeded
Yes
Upper endstop
7
limit exceeded
No
Deadband limit
8
exceeded
Yes
Case 1: Reference
9
stroke time for
partial stroke test
is exceeded.
Case 2: Start posi-
tion outside the
start tolerance
224
Parameter setting
Error message disappears
when
Always active
... the actual-value response
falls below the value for LIM
... the device is changed to
**. FCT
1)
"Automatic" mode.
= nA or =
nAB
... the binary input is no long-
**.
FCT
1)
er active.
= nAB and binary
function BIN1 or
BIN2 on "On"
... the stroke counter is reset
L. STRK≠OFF
or the thresholds are in-
creased
... the counter for changes of
O. DCHG≠OFF
direction is reset or the
thresholds are increased.
... the deviation of the end-
F. ZERO≠OFF
stop disappears or the device
**.YCLS = do or up
is re-initialized.
do
... the deviation of the end-
G. OPEN≠OFF
stop disappears or the device
**.YCLS
= do or
1)
is re-initialized.
up do
... the limit is undershot again
E. DEBA≠OFF
**.DEBA
= Auto
1)
Case 1: ... a partial stroke test
A. PST≠OFF
is successfully executed
within the reference stroke
time or the function is deac-
tivated.
Case 2: Move the actuator
into the range of the PST
start tolerance. Or increase
the PST start tolerance until
the actuator (PST start posi-
tion) is within the PST start
tolerance. Start the partial
stroke test again.
Possible causes
Compressed air failure, actu-
ator fault, valve fault (e.g.
blockade).
The device has been config-
ured or is in the manual mode
The contact connected to the
binary input was active (e.g.
packing gland monitoring,
overpressure, temperature
switch).
The total path covered by the
actuator exceeds one of the
configured thresholds.
The number of changes of
direction exceeds one of the
configured thresholds.
Wear and tear of the valve
seat, deposits or foreign bod-
ies in the valve seat, mechan-
ical misalignment, friction
clutch moved.
Wear and tear of the valve
seat, deposits or foreign bod-
ies in the valve seat, mechan-
ical misalignment, friction
clutch moved.
Increased packing gland
friction, mechanical gap in the
position feedback.
Case 1: Valve is stuck or
rusted. Increased stiction.
Case 2: Valve is present in
the safety position.