Alarm, error, and system messages
10.2 Diagnostics
How to show the diagnostics values in reverse order
Press the
How to set values to zero
Specific values can be set to zero by pressing the
diagnostics values which can be reset are listed in the table in section "Overview of
diagnostics values (Page 206)".
10.2.2

Overview of diagnostics values

Explanatory notes on the following table
● The "Representable diagnostics values" column shows the factory settings for the
diagnostics parameters in bold type.
● The "Reset possible" column contains an "X" if the diagnostics value can be set to zero.
● The "Properties" column shows the properties of the diagnostics parameters:
Overview of diagnostics values
No.
Abbreviation
Meaning
1
STRKS
Number of total strokes
2
CHDIR
Number of changes in direction
3
Number of fault messages
CNT
4
A1CNT
Number of alarms 1
5
A2CNT
Number of alarms 2
6
HOURS
Number of operating hours
7
HOURR
Resettable operating hours counter
8
WAY
Determined actuator travel
9
TUP
Travel time UP
10
TDOWN
Travel time DOWN
206
and
buttons simultaneously.
Diagnostics value can be read and reset.
Diagnostics value can be read but not reset.
Diagnostics value can be read but not reset. A function can be executed.
Diagnostics value can be read, manually reset, and manually changed.
button for at least 5 seconds. The
Representable
Unit
diagnostics val-
ues
0 ... 4.29E9
-
0 ... 4.29E9
-
0 ... 4.29E9
-
0 ... 4.29E9
-
0 ... 4.29E9
-
0 ... 4.29E9
Hours
0 ... 4.29E9
0 ... 130
mm or °
0.0 / 0 ... 1000
s
0.0 / 0 ... 1000
s
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Properties