Siemens 6DR50 Series Operating Instructions Manual page 188

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Parameterizing/addressing
9.4 Description of parameters
d1.LIMIT - limit for slipstick detection
Adjustment range:
Purpose:
Factory setting:
d2.FACT1 - Factor 1
Adjustment range:
Purpose:
Factory setting:
d3.FACT2 - Factor 2
Adjustment range:
Purpose:
Factory setting:
d4.FACT3 - Factor 3
Adjustment range:
Purpose:
Factory setting:
186
0.1 ... 100.0 %
Use this sub-parameter to set the base limit for slipstick detection
in percent. Set the base limit in a range from "0.1" to "100.0".
1.0 %
0.1 ... 100.0 %
Use this sub-parameter to set the factor for the formation of limit
threshold 1. Set the factor in a range from "0.1" to "100.0". The
limit threshold is the product of the values entered for "d1.LIMIT"
and "d2.FACT1".
The threshold 1 error message is displayed when the limit thresh-
old 1 is exceeded. The procedure to activate and display this error
message is described in the "XDIAG" parameter.
2.0
0.1 ... 100.0 %
Use this sub-parameter to set the factor for the formation of limit
threshold 2. Set the factor in a range from "0.1" to "100.0". The
limit threshold is the product of the values entered for "d1.LIMIT"
and "d3.FACT2".
The threshold 2 error message is displayed when the limit thresh-
old 2 is exceeded. The procedure to activate and display this error
message is described in the "XDIAG" parameter.
5.0
0.1 ... 100.0 %
Use this sub-parameter to set the factor for the formation of limit
threshold 3. Set the factor in a range from "0.1" to "100.0". The
limit threshold is the product of the values entered for "d1.LIMIT"
and "d4.FACT3".
The threshold 3 error message is displayed when the limit thresh-
old 3 is exceeded. The procedure to activate and display this error
message is described in the "XDIAG" parameter.
10.0
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12