Overview Of Application Parameters 6 To 52 - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Parameterizing/addressing
9.3 Parameter overview
Set the transmission ratio selector accordingly.
1)
Parameter only appears with "WAY", "-WAY", "ncSLL", and "-ncLL"
2)
If used, the value on the actuator must correspond to the set range of stroke on the lever arm.
3)
Carrier must be set to the value of the actuator travel or, if this value is not scaled, to the next larger scale value.
9.3.2

Overview of application parameters 6 to 52

Introduction
These parameters are used to configure the following additional functions of the positioner:
● Setpoint preparation
● Actual value preparation
● Binary signal processing
● Tight closing function
● Limit detection
Note
Factory-set parameter values are printed in bold in the following table.
148
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12