Siemens 6DR50 Series Operating Instructions Manual page 138

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Commissioning
7.6 Commissioning part-turn actuators
9. Press the
the following:
Note
Fault message "RANGE"
The selected end position is beyond the permissible measuring range if the "RANGE"
message is output on the display. Correct the settings as follows:
1. Move the friction clutch until the display shows "OK".
2. Press the
3. Move the actuator to another position using the
4. Abort the manual initialization process by pressing the
5. Then return to "P manual mode" mode.
6. Correct the actuator travel and the position detection.
10.Determine the upper endstop of the actuator. Move the actuator to the desired position
using the
11.Press the
12.The initialization process is automatically resumed. Initialization steps "RUN1" to "RUN5"
are output in the bottom line of the display. The following display indicates that the
initialization has been completed successfully:
Aborting the manual initialization process
1. Press the
"Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the
3. The software status is displayed.
4. After releasing the
means that the positioner has not been initialized.
136
button. The current position of the actuator is applied. The display shows
button.
or
button.
button. The current position of the actuator is applied.
button. The display shows the "INITM" parameter. The positioner is in the
button, the positioner is in "P manual mode". "P manual mode"
or
button.
button.
button for at least 5 seconds.
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12