5. Call the "5.INITM" parameter. To do this, press the
the following:
6. Start the initialization process. To do this, press the
the display shows the following:
The current potentiometer position is output on the display after 5 seconds. Examples of
the displayed potentiometer positions are given below:
7. Determine the lower endstop of the actuator spindle.
8. Move the actuator to the desired position using the
9. Press the
the following:
Note
Fault message "RANGE"
The selected end position is beyond the permissible measuring range if the "RANGE"
message is output on the display. Correct the settings as follows:
1. Move the friction clutch until the display shows "OK".
2. Press the
3. Move the actuator to another position using the
4. Abort the manual initialization process by pressing the
5. Then return to "P manual mode" mode.
6. Correct the actuator travel and the position detection.
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
button. The current position of the actuator is applied. The display shows
button.
Commissioning
7.5 Commissioning linear actuators
button twice. The display shows
button for at least 5 seconds until
or
button.
or
button.
button.
129