OVERVIEW
®
The Simplicity
LINC Gateway operates as a Modbus® Client
providing an interface between a BACnet® MS/TP control system
and devices that communicate using the Modbus RTU protocol.
®
The Simplicity
LINC allows monitoring and control by a third-party
BACnet Building Automation System (BAS).
®
The Simplicity
LINC is preconfigured to provide an interface to UP
products equipped with Simplicity
4/2/2008 as well as prior Simplicity
Intelli-Comfort™ controllers.
R
C
24 — must be grounded
close to the
24V power is polarity sensitive, incorrect
wiring could result in board damage.
FIGURE 1: WIRE CONNECTIONS
APPLICATION GUIDE
Simplicity
®
controllers manufactured after
®
Elite™ and Simplicity
®
LINC
®
LINC GATEWAY
The Simplicity
unit and utilizes 24 VAC power from the unit's control transformer.
One port is connected to the UP controller. The other port must be
connected to the BACnet MS/TP network.
The Simplicity
operational data points from the controller and expose them on a
BACnet MS/TP network.
NOTE: Not all Simplicity
monitored by the Simplicity
®
with
®
LINC mounts inside the control panel of the UP
®
LINC Gateway is preconfigured to obtain
®
operating parameters are controlled/
®
LINC.
The shield must be
connected to ground at
each device.
514067-UAD-A-0509

Advertisement

loading

Summary of Contents for York LINC GATEWAY 514067-UAD-A-0509

  • Page 1 The Simplicity LINC is preconfigured to provide an interface to UP ® products equipped with Simplicity controllers manufactured after ® 4/2/2008 as well as prior Simplicity Elite™ and Simplicity Intelli-Comfort™ controllers. 24 — must be grounded ® close to the...
  • Page 2: Modbus Connection

    LINC to other devices and must be between 1 and 99. The default DIP switch setting is 1. A Device Instance (DE) Modifier is used by the Simplicity and defaulted to 230. The combination of the DE Modifier and the default DIP switch setting creates a default DE of 23001.
  • Page 3: Flash Memory Management

    FLASH MEMORY MANAGEMENT The Flash Memory chip used in the Simplicity a 1,000,000 write cycle rating. To prevent premature failure of the flash memory, it should not be written to more often than once every 10 minutes, on average. Under unusual circumstances it could take up to two minutes for newly updated data to be seen.
  • Page 4 514067-UAD-A-0509 TABLE 2: POINTS LIST IN DESCRIPTION ORDER BACnet BACnet Read/ Object Object Write Type Inst (2) AV (2) AV (5) BV (2) AV (5) BV (5) BV (5) BV (5) BV (5) BV (2) AV (5) BV (2) AV (2) AV (5) BV (5) BV...
  • Page 5 TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) BACnet BACnet Read/ Object Object Write Type Inst (2) AV (5) BV (5) BV (2) AV (5) BV (2) AV (2) AV (2) AV (2) AV (2) AV (5) BV (5) BV (2) AV (5) BV (5) BV...
  • Page 6 514067-UAD-A-0509 TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) BACnet BACnet Read/ Object Object Write Type Inst (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (2) AV (5) BV (5) BV...
  • Page 7 TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) BACnet BACnet Read/ Object Object Write Type Inst (5) BV (2) AV (5) BV (5) BV (2) AV (2) AV (2) AV (2) AV (5) BV (2) AV (5) BV (5) BV (5) BV (5) BV (5) BV...
  • Page 8 514067-UAD-A-0509 TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) BACnet BACnet Read/ Object Object Write Type Inst (5) BV (5) BV (2) AV (2) AV (5) BV (5) BV (2) AV (5) BV (2) AV (2) AV (2) AV (5) BV (2) AV (5) BV (2) AV...
  • Page 9 TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) BACnet BACnet Read/ Object Object Write Type Inst (2) AV (2) AV (5) BV (2) AV (2) AV (2) AV (2) AV (5) BV (2) AV (5) BV (2) AV (2) AV (2) AV (2) AV (2) AV...
  • Page 10 514067-UAD-A-0509 TABLE 3: POINTS LIST IN OBJECT ORDER BACnet BACnet Read/ Object Object Write Type Inst (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV...
  • Page 11 TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) BACnet BACnet Read/ Object Object Write Type Inst (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV...
  • Page 12 514067-UAD-A-0509 TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) BACnet BACnet Read/ Object Object Write Type Inst (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV (2) AV...
  • Page 13 TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) BACnet BACnet Read/ Object Object Write Type Inst (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV...
  • Page 14 514067-UAD-A-0509 TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) BACnet BACnet Read/ Object Object Write Type Inst (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV...
  • Page 15 TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) BACnet BACnet Read/ Object Object Write Type Inst (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV (5) BV...
  • Page 16: Troubleshooting

    ® The Simplicity LINC Gateway consists of two printed circuit boards. ® TABLE 4: SIMPLICITY LINC GATEWAY RS485 BOARD (Bottom) Normal Board Operation The PWR LED should be on during operation. The RX and TX LEDs should flash when a signal is either received or sent.
  • Page 17 (BACnet) (BACnet) (BACnet) (RS485) ® FIGURE 3: SIMPLICITY LINC GATEWAY LED LOCATION Johnson Controls Unitary Products 514067-UAD-A-0509 (RS485) (BACnet) GP105 (BACnet) (BACnet) (RS485)
  • Page 18 Subject to change without notice. Printed in U.S.A. Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069 514067-UAD-A-0509 Supersedes: Nothing...