21
P100
Potentiometer value upper stop (100%)
22
IMPUP
Pulse length up (Impulse Length Up)
23
IMPDN
Pulse length down (Impulse Length Down)
24
DBUP
Dead zone up (Dead Band Up)
25
DBDN
Dead zone down (Dead Band Down)
26
SSUP
Short step zone up (Short Step Zone Up)
27
SSDN
Short step zone down (Short Step Zone Down)
28
TEMP
Current temperature
29
TMIN
Minimumtemperature ("min/max pointer")
30
TMAX
Maximumtemperature ("min/max pointer")
31
T1
Number of operating hours in temperature range 1
32
T2
Number of operating hours in temperature range 2
33
T3
Number of operating hours in temperature range 3
34
T4
Number of operating hours in temperature range 4
35
T5
Number of operating hours in temperature range 5
36
T6
Number of operating hours in temperature range 6
37
T7
Number of operating hours in temperature range 7
38
T8
Number of operating hours in temperature range 8
39
T9
Number of operating hours in temperature range 9
40
VENT1
Number of switching operations pilotvallve 1
41
VENT2
Number of switching operations pilotvallve 2
42
STORE
Save current values as "last maintenance"
(press increment button for 5s) (Store)
43
PRUP
Prediction up
44
PRDN
Prediction down
45
WT00
Number of operating hours in actuating range WT00
46
WT05
Number of operating hours in actuating range WT05
47
WT10
Number of operating hours in actuating range WT10
48
WT30
Number of operating hours in actuating range WT30
49
WT50
Number of operating hours in actuating range WT50
50
WT70
Number of operating hours in actuating range WT70
51
WT90
Number of operating hours in actuating range WT90
52
WT95
Number of operating hours in actuating range WT95
53
mA
Setpoint current
Table 4-1
Overview of diagnosis values
4.5.2 Meaning of the diagnosis values
1 STRKS
2 CHDIR
SIPART PS2 Manual
A5E00074631--06
Number of strokes
During operation, the actuator movements are added up and can be
read off here as the number of strokes. Unit: 100% strokes, i.e. the
path between 0 and 100 % and back. The value is written into a
non-volatile memory every 15 minutes. It can be set to zero with the
increment button
.
Number of changes of direction
Operation
Values than
Unit
can be
indicated
0.0 to 100.0
%
2 to 160
ms
2 to 160
ms
0.1 to 10.0
%
0.1 to 10.0
%
0.1 to 100.0
%
0.1 to 100.0
%
--40 to 85
_C
--40 to 85
_C
--40 to 85
_C
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
--
0 to 4.29E9
--
--
--
1 to 40
--
1 to 40
--
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0 to 4.29E9
hours
0.0 to 20.0
mA
Reset
possible
x
x
x
x
x
x
x
x