Fault description (symptoms)
SIPART PS2 comes to a halt in
RUN 3
SIPART PS2 comes to a halt in
RUN 5, does not reach FINISH
(waiting time > 5 min)
Table 1
Fault description (symptoms)
CPU test blinks in the display of the
SIPART PS2 (ca. every 2 secs)
Piezo valve(s) do not switch
Actuator cannot be moved in
manual or automatic mode, or only
in one direction
Piezo valve(s) do not switch (no
soft clicking can be heard when the
+ or -- keys are pressed in manual
mode)
Table 2
Fault description (symptoms)
Actuator does not move
Piezo valve(s) do not switch (al-
though a soft clicking can be
heard when the + or -- keys are
pressed in manual mode)
One piezo valve constantly
switches in stationary automatic
mode (constant setpoint) and in
manual mode
Table 3
SIPART PS2
A5E00074600-05
Possible cause(s)
Actuator positioning time too long
Play in the positioner, actuator,
fittings system
Possible cause(s)
Water in the valve manifold (from
wet compressed air)
Dampness in the valve manifold
Screw between cover hood and the
valve manifold is not tight or the
hood is jammed
Dirt (swarf, particles) in the valve
manifold
Deposits on the contact(s) between
the electronics board and the valve
manifold can occur from abrasion
through continuous stresses from
strong vibrations
Possible cause(s)
Compressed air < 1.4 bar
Restrictor(s) closed down
(screw(s) at the right end stop)
Dirt in the valve manifold
Pneumatic leak in the positioner,
actuator system, start leak test in
RUN 3 (Initialization) !!!
Dirt in the valve manifold (see
above)
Operating instructions
Corrective actions
Open restrictor fully and/or set
pressure PZ(1) to the highest
permissible value
Use booster if necessary
Linear actuator:
Check seating of the stud screw of
the coupling wheel
Rotary actuator:
Check seating of the lever on the
positioner shaft
Correct any other play between the
actuator and the fittings
Corrective actions
At the early stages the fault can be
corrected by subsequent operation
with dry air (when necessary, in a
temperature cupboard at 50 to
temperature cupboard at 50 to
70 °C)
Otherwise: Repair at CSC (see
page 66)
Tighten screw, or release cause of
jamming when necessary
1)
Repair at CSC
or new device with
integrated fine filter which can be
replaced and cleaned
Clean all contact surfaces with alco-
hol: when necessary bend the valve
manifold contact springs back into
place
Corrective actions
Set inlet air pressure to > 1.4 bar
Open restrictor screw(s) (see leaf-
let, Figure "View of device (6)") by
turning to the left
1)
Repair at CSC
or new device
with integrated fine filter which can
be replaced and cleaned
Fix leak in the actuator and/or
supply line
If the actuator and supply line are
intact:
Repair of SIPART PS 2 at CSC
or new device
See above
1)
65