Siemens sipart ps2 Operating Instructions Manual page 19

Electropneumatic positioner
Hide thumbs Also See for sipart ps2:
Table of Contents

Advertisement

Operating instructions
6.
Start initialization by pressing the increment key for more than 5 s.
Display:
7.
After 5 s, the display changes to:
Display:
(The display of the potentiometer setting is shown here and in the following as an example only).
Drive the actuator with the increment (+) and decrement (--) keys to the position that you wish to define as
the first of the two end positions. Then press the mode key
as end position 1 and will switch to the next step.
.
NOTE
If the message RANGE appears in the lower line, the selected end position is outside the
permissible measuring range. There are several options to correct this error:
S Adjust the friction clutch until OK appears and then press the mode key once more, or
S Drive to another end position with the increment and decrement keys, or
S Interrupt the initialization by pressing the mode key. Then you have to switch to P--Manual mode
and correct the travel and the position measurement according to step 1.
8.
When step 7 has been completed successfully, the following display appears:
Display:
Now drive the actuator with the increment (+) and decrement (--) keys to the position that you wish to define
as the second end position. Then press the mode key
the end position 2.
.
NOTE
If the message RANGE appears in the lower line, the selected end position is outside the permitted
measuring range or the measuring span is too small. There several options to correct this error:
S Drive to another end position with the increment and decrement keys, or
S Interrupt the initialization by pressing the mode key. Then you have to switch to P--Manual mode
and correct the travel and the position measurement according to step 1.
.
NOTE
If the message Set Middle appears, the lever arm must be moved to the horizontal position with the
increment and decrement keys and then the mode key pressed. This sets the reference point of the
sine correction for linear actuators.
9.
The rest of the initialization occurs automatically. RUN1 through to RUN5 appear in the lower line of the dis-
play sequentially. When the initialization has been completed successfully, the following display appears:
Display:
60
. In this way the current position is taken over
. The current position will now be taken over as
SIPART PS2
A5E00074600-05