Fig. 6
Pneumatic connection
Two pneumatic connections for the integrated installation of single--acting linear actuators are located on the rear
of the positioner:
Positioning pressure Y1
-
Air outlet E
-
These connections are locked with screws when supplied.
Outlet air E can be used to ensure a flow of dry instrument air through the pick--off area and the spring chamber
to prevent corrosion.
Procedure:
Connect manometer for inlet air pressure and positioning pressure in necessary.
-
Connection via female thread G 1/4 DIN 45141:
-
PZ
Inlet air 1.4 to 7 bar
Y1
Positioning pressure 1 for single-action and double-action actuators
Y2
Positioning pressure 2 for double-action actuators
E
Exhaust output (remove silencer if necessary)
Safety setting on failure of electric supply:
-
single-action:
Y1 Vented
double-action: Y1 Max. positioning pressure (inlet air pressure)
Y2 Vented
Connect positioning pressure Y1 or Y2 (only with double-action actuators) according to desired safety
-
setting.
Connect inlet air to PZ.
-
.
NOTE
Spring return actuators need sufficient high supply pressure so that the complete stroke can be travelled
up to the end position of the actuator.
SIPART PS2
A5E00074600-05
Positioning pressure Y1 for single and double--acting actuators
Feedback shaft
Inlet air P
Z
Positioning pressure Y2 for double--acting actuators
Outlet air E with silencer on the underside of the instrument
Operating instructions
55