VYPER/MOD D VARIABLE SPEED DRIVE SCREEN

FIGURE 31 - VYPER/MOD D VARIABLE SPEED DRIVE SCREEN

OVERVIEW
This screen displays information pertaining to a Vyper/
Mod D Variable Speed Drive (VSD).
DISPLAY ONLY
PRV Position
Displays the Pre-rotation Vane position as a value be-
tween 0 and 100%.
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
% Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value.
Current Limit Setpoint
Displays the current limit value in use. This value could
come from a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2
to 10VDC input in Analog Remote mode, PWM signal
in Digital Remote mode, E-Link Gateway interface in
ISN mode, or a locally programmed value.
JOHNSON CONTROLS
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Output Voltage
Displays the output voltage measured to the motor.
VSD Output Frequency
Displays the present output frequency to the motor.
Input Power
Displays the total kilowatts measured by the VSD or
Harmonic Filter, if installed.
KW Hours
Displays the cumulative amount of kilowatts used over
time as the VSD motor controller operates.
Output Current – Phase A, B, C
Displays the phase current measured to the motor.
Voltage Total Harmonic Distortion –
(L1, L2, L3) Displays the Total Harmonic Distortion
(THD) for each of the voltage lines as calculated by
the filter.
Supply Current Total Demand Distortion –
(L1, L2, L3) Displays the Total Dynamic Distortion
(TDD) for each of the supply current lines as calcu-
lated by the filter.