Mod "B" Solid State Starter Screen; Figure 29 - Mod "B" Solid State Starter Screen - York YK Style H Operation Manual

With optiview control center centrifugal liquid chillers, for electro-mechanical starter, solid state starter and variable speed drive
Hide thumbs Also See for YK Style H:
Table of Contents

Advertisement

FORM 160.76-O2
issue date: 6/15/2015

MOD "B" SOLID STATE STARTER SCREEN

FIGURE 29 - MOD "B" SOLID STATE STARTER SCREEN

OVERVIEW
This screen displays all information pertaining to the
Mod "B" Solid State Starter.
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value.
Current Limit Setpoint
Displays the current limit in use. This value could
come from a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2
to 10VDC input in Analog Remote mode, PWM signal
in Digital Remote mode, E-Link Gateway interface in
ISN Remote mode or a locally programmed value in
Local mode.
Pulldown Demand Time Left
Displays the time remaining in the programmed
pulldown period.
JOHNSON CONTROLS
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Input Power
Displays the kilowatts measured by the Solid State
Starter.
KW Hours
Displays the cumulative amount of kilowatts used over
time.
Starter Model
Displays the Solid State Starter model that is applied
to the chiller. Starter Models are 7L, 14L, 26L or 33L.
Voltage – Phase A, B, C
Displays the 3-phase input line voltage measured by
the Solid State Starter.
Current – Phase A, B, C
Displays the 3-phase motor current values measured
by the Solid State Starter.
Temperature – Phase A, B, C
Displays the temperatures of the Silicon Controlled
Rectifier assemblies.
LD10708a
85
2