SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION

TABLE 2 - CAPACITY CONTROL SETPOINT PROGRAMMABLE SETTINGS

PROGRAM SETTING
LCHLT Setpoint Ramp Rate
LCHLT Setpoint Start Offset
Default Capacity Control Setpoints
Cooling Control Kp
Cooling Control Ti
Cooling Control Td
Heating Control Kp
Heating Control Ti
Heating Control Td
Temperature Control Max Loading
Delta
Temperature Control Max
Unloading Delta
VSD Output Gain
VGD Output Gain
PRV Output Gain
HGBP Output Gain
Gear Ratio Override
Motor Slip Factor
Impeller Diameter Override
56
ACCESS LEVEL/
LOW LIMIT
STATE
Service
Service
0.0 ºF (differential)
Service
Choice: Yes
Admin
Admin
Admin
Admin
Admin
Admin
Admin
Admin
Admin
Admin
Admin
Admin
Admin and Stopped
Admin
Admin and Stopped
HIGH LIMIT
0.1 ºF/s
2.0 ºF/s
10.0 ºF (differential)
Yes
0.1
15.0
0.1
200.0
0.0
200.0
0.1
15.0
0.1
200.0
0.0
200.0
0.1
100.0
0.1
100.0
0.1
10.0
0.1
10.0
0.1
10.0
0.1
10.0
0.0000
7.0000
0.980
1.000
0.0000
1.0000
FORM 160.76-O2
issue date: 6/15/2015
DEFAULT
0.1 ºF/s
5.0 ºF (differential)
5.0
25.0
0.0
5.0
25.0
0.0
1.0
1.0
0.5
1.0
1.0
1.0
0.0000
0.992
0.0000