York YK Style H Operation Manual page 32

With optiview control center centrifugal liquid chillers, for electro-mechanical starter, solid state starter and variable speed drive
Hide thumbs Also See for YK Style H:
Table of Contents

Advertisement

SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Condenser Pressure
Displays the refrigerant pressure in the condenser.
Leaving Heating Condenser Liquid Tempera-
ture
Displays the temperature of the liquid as it leaves the
heating condenser tube bundle. Only appears when the
Heat Recovery is enabled.
Entering Heating Condenser Liquid Tempera-
ture
Displays the temperature of the liquid as it enters the
heating condenser tube bundle. Only appears when the
Heat Recovery is enabled.
Heating Condenser Liquid Flow Switch (LED)
Displays the status of the flow switch in the heating
condenser tube bundle. Illuminates when liquid flow
is present. Otherwise, it is extinguished. Only appears
when the Heat Recovery is enabled.
Condenser Liquid Flow Switch (LED)
Displays the status of the flow switch in the standard
condenser tube bundle. Illuminates when liquid flow
is present. Otherwise, it is extinguished. Only appears
when the Heat Recovery is enabled.
Drop Leg Refrigerant Temp
Displays the temperature of the refrigerant in the drop
leg between the condenser and evaporator shells, if the
sensor is present.
Subcooling Temperature
Displays the difference between the Condenser Re-
frigerant temperature and the Drop Leg Refrigerant
temperature. The Condenser Refrigerant temperature
will be represented by the Condenser Saturation tem-
perature. If the Drop Leg Sensor is not present, this
temperature is not displayed.
High Pressure Switch (Open / Closed)
Displays the present position of the high pressure
switch. This will indicate whether a high pressure fault
is present.
Condenser Liquid Flow Switch
Indicates whether flow is present in the condenser.
Condenser Liquid Pump (Run / Stop)
Indicates whether condenser liquid pump is operating.
32
Condenser Refrigerant Level
Displays the present position of the refrigerant level if
this function is enabled.
Active Level Setpoint
Displays the setpoint to which the refrigerant level is
being controlled.
Level Control Valve Command
Displays the value of the refrigerant valve position
command.
For fields requiring access level of SER-
VICE. Service Technicians refer to the
OptiView Control Center - Service Instruc-
tions (Form 160.76-M1) for operation
instructions and explanation of all pro-
grammable setpoints and displayed values.
PROGRAMMABLE
High Pressure Warning Threshold
Access Level Required: SERVICE
This value allows the user to define the condenser pres-
sure at which the chiller will initiate a warning.
When Heat Pump Duty is set to enabled, this setpoint
is automatically set to 193 PSIG.
Drop Leg (Enabled / Disabled)
Access Level Required: SERVICE
When a Drop Leg Refrigerant Sensor has been installed
it must be enabled via this toggle before the system
will utilize the new, enhanced resolution input.
Fault Acknowledge
Access Level Required: SERVICE
This allows clearing of the High Condenser Pressure
Fault while Shutdown (Condenser-High Pressure
Stopped).
NAVIGATION
Home
Access Level Required: VIEW
Returns user to HOME Screen.
Level Control
Access Level Required: SERVICE
Moves to the subscreen allowing programming of the
refrigerant liquid level control setpoints.
FORM 160.76-O2
issue date: 6/15/2015
JOHNsON CONtROLs