FIGURE 9 - CONDENSER SCREEN

OVERVIEW
This screen displays a cutaway view of the chiller con-
denser. All setpoints relating to the condenser side of
the chiller are maintained on this screen. Animation in-
dicates condenser liquid flow. When Heat Recovery is
enabled, the condenser flow animation will show flow
when either the Condenser Liquid Flow Switch or the
Heating Condenser Liquid Flow Switch says flow is
present. When Heat Recovery is disabled, the condens-
er flow animation is based on the standard Condenser
Flow Switch. This screen also serves as a gateway to
controlling the Refrigerant Level, Heat Recovery and
Head Pressure Control.
DISPLAY ONLY
Leaving Condenser Liquid Temperature
Displays the liquid temperature as it leaves the con-
denser.
JOHNSON CONTROLS
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION

CONDENSER SCREEN

Leaving Condenser Liquid Temperature
Setpoint
Displays the active setpoint to which the Heat Pump
is controlling the Leaving Condenser Liquid Tempera-
ture. Only displayed when Heat Pump is enabled on
the SETUP Screen and the Operation mode is set to
Heating mode on the HEAT PUMP Screen.
Entering Condenser Liquid Temperature
Displays the water temperature as it enters the condenser.
Condenser Saturation Temperature
Displays the saturation temperature in the condenser.
Condenser Small Temperature Difference
Displays the difference between the Condenser Refrig-
erant temperature and the Leaving Condenser Liquid
temperature. The Condenser Refrigerant temperature
will be represented by the Condenser Saturation tem-
perature.