Printer Setup; Control Center Setup; Downloading System Prints To Alaptop - York YK Style H Operation Manual

With optiview control center centrifugal liquid chillers, for electro-mechanical starter, solid state starter and variable speed drive
Hide thumbs Also See for YK Style H:
Table of Contents

Advertisement

FORM 160.76-O2
issue date: 6/15/2015

PRINTER SETUP

The selected printer must be configured as follows. Re-
fer to manual provided by printer manufacturer with
respective printer.
OKIDATA OKIPOS 441
1. With the printer power off, remove the two screws
which hold the RS232 Interface Module.
2. Pull the RS232 Interface Module out of the printer.
3. Set DIP switch SW2-2 to OFF to select 19200
BPS. Do not change any other switch settings.
4. Re-install the RS232 Interface Module and two
mounting screws.
5. Load paper and install the printer ribbon into the
printer.
6. Connect the printer cable to the printer and the
microboard.
7. Connect the printer power cable to the printer and
plug into a 100 to 240VAC power source.

CONTROL CENTER SETUP

Chiller ID
Access Level Required: OPERATOR
Using the COMMS Screen, assign an identification
number to the chiller. This number will appear at the
top of each report.
Printer Setup
Access Level Required: OPERATOR
Using the COMMS Screen, the Control Center must be
configured to transmit data in the same format as the
printer is configured to receive the data. The following
values must be entered.
• Baud Rate - Set to 19200
• Data Bits - 8
• Parity - None
• Stop Bits - 1
JOHNSON CONTROLS
Printer Type
Access Level Required: OPERATOR
Using the PRINTER Screen, set the printer type to
Weigh-Tronix.
Automatic Data Logging
Access Level Required: OPERATOR
If automatic data logging is desired, a status report can
be automatically printed at a specified interval begin-
ning at a specified time, using the PRINTER Screen.
The interval is programmable over the range of 1 min-
ute to 1440 minutes in 1 minute increments. The first
print will occur at the programmed START time and
occur at the programmed Output Interval thereafter.
The time remaining until the next print is displayed on
the PRINTER Screen.
• Automatic Printer Logging - Enables and disables
automatic data logging.
• Log Start Time - Enter the time the first print is
desired.
• Output Interval - Enter the desired interval be-
tween prints.
DOWNLOADING SYSTEM PRINTS TO A
LAPTOP
Downloading system histories to a file is another use-
ful method to capture system operating conditions. The
following instructions are used to establish communi-
cation between the OptiView Control Panel and a lap-
top computer.
1. Connect the laptop computer to the OptiView as
described below.
Laptop
(RS-232 Serial Port)
PIN
DESC
2
RX
to
4
DTR
to
5
GND
to
2. On OptiView Printer Screen, select "PC". This
will allow faster data download than the printer
selections. SETTINGS should match "H. Port set-
tings" see below. Earlier software select SEIKO if
PC selection is not available.
SECTION 4 - PRINTING
OptiView
(Com 1)
Connector Terminal
J2
4 (TXD1)
J2
2 (DSR1)
J2
9 GND
191
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents