York YK Style H Operation Manual page 164

With optiview control center centrifugal liquid chillers, for electro-mechanical starter, solid state starter and variable speed drive
Hide thumbs Also See for YK Style H:
Table of Contents

Advertisement

SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
TABLE 4 - MASTER SLOT NUMBERS LIST FOR
USE WITH TREND FEATURE (CONT'D)
SLOT
NUMBER
2847
ACC: Surge Margin
2848
ACC: Manual Surge Command
2849
ACC: Surge Map Count
2850
ACC: Surge Type
2857
ACC: Surge Map Point Count
2858
ACC: Surge Map Delta P/P
2859
ACC: Surge Map Output Frequency
2860
ACC: Surge Map PRV Position
2861
Filter: Is Filter Installed
2862
Filter: Is Operation Inhibited
2863
Filter: Is Filter Running
2864
Filter: Is Precharge Contactor Closed
2865
Filter: Is Supply Contactor Closed
2866
Filter: Phase Rotation
2867
Filter: Motor HP
2868
Filter: Supply kVA
2869
Filter: Total Power Factor
2870
Filter: DC Bus Voltage
2871
Filter: Heatsink Temperature
2872
Filter: L1 - L2 RMS Voltage
2873
Filter: L2 - L3 RMS Voltage
2874
Filter: L3 - L1 RMS Voltage
2875
Filter: L1 - N Peak Voltage
2876
Filter: L2 - N Peak Voltage
2877
Filter: L3 - N Peak Voltage
2878
Filter: L1 Total Harmonic Distortion
2879
Filter: L2 Total Harmonic Distortion
2880
Filter: L3 Total Harmonic Distortion
2881
Filter: L1 RMS Filter Current
2882
Filter: L2 RMS Filter Current
2883
Filter: L3 RMS Filter Current
2884
Filter: L1 RMS Supply Current
2885
Filter: L2 RMS Supply Current
2886
Filter: L3 RMS Supply Current
2887
Filter: L1 Total Demand Distortion
2888
Filter: L2 Total Demand Distortion
2889
Filter: L3 Total Demand Distortion
2890
Filter: Maximum Total Harmonic Distortion
2891
Filter: Maximum Total Demand Distortion
8192
Oil: Pump Pressure
8193
Oil: Sump Pressure
8194
Oil Seal Lube: Is Control Enabled
8195
Oil Seal Lube: Time To Next Lube
164
DESCRIPTION
TABLE 4 - MASTER SLOT NUMBERS LIST FOR
USE WITH TREND FEATURE (CONT'D)
SLOT
NUMBER
8196
Oil Seal Lube: Time Left
8197
VSOP: Speed Command
8198
VSOP: Control Mode
8199
VSOP: Manual Command Frequency
8200
VSOP: Is Pulldown In Effect
8201
VSOP: Pulldown Time Remaining
8202
VSOP: Target Setpoint
8203
VSOP: Pressure Setpoint
8204
VSOP: Control Period
8205
Refrigerant Level: Is Control Enabled
8206
Refrigerant Level: Position
8207
Refrigerant Level: Is Valve Closing
8208
Refrigerant Level: Is Valve Opening
8209
Refrigerant Level: Control Mode
8210
Refrigerant Level: Is Pulldown In Effect
8211
Refrigerant Level: Pulldown Time Remaining
8212
Refrigerant Level: Target Setpoint
8213
Refrigerant Level: Setpoint
8214
Refrigerant Level: Period
8215
Refrigerant Level: Proportional Limit Close
8216
Refrigerant Level: Proportional Limit Open
8217
Refrigerant Level: Rate Limit Close
8218
Refrigerant Level: Rate Limit Open
8222
HSTB: Is Solenoid Installed
8223
HSTB: Is Solenoid On
8224
HSTB: Proximity Position
8225
HSTB: Proximity Differential
8226
HSTB: Proximity Reference Position
8280
Stall Detector Board output voltage
8281
VGD open
8282
VGD close
8317
Stall DC Pressure Voltage
FORM 160.76-O2
issue date: 6/15/2015
DESCRIPTION
JOHNsON CONtROLs