Trend Screen; Figure 56 - Trend Screen - York YK Style H Operation Manual

With optiview control center centrifugal liquid chillers, for electro-mechanical starter, solid state starter and variable speed drive
Hide thumbs Also See for YK Style H:
Table of Contents

Advertisement

FORM 160.76-O2
issue date: 6/15/2015

FIGURE 56 - TREND SCREEN

OVERVIEW
As many as six Operator selected parameters (Data
Points) can be plotted in an X/Y graph format. The
X-Axis is scaled per the selected Data Collection In-
terval and displayed in a time of day or elapsed time
format, as selected with the X-Axis TOGGLE key. The
Y-Axis is scaled for each parameter per the selected
minimum and maximum value for each parameter.
Analog parameters are scaled in pressure, temperature,
volts, amps, hertz or time. Digital on/off parameters
are scaled as zero (off) and one (on). Only one Y-Axis
label is displayed at a time. The Y-Axis TOGGLE Key
is used to toggle the Y-Axis labels through the different
parameters. The Y-Axis label that is being displayed
is identified at the top of the graph. For identification,
each plotted parameter and associated Y-Axis labeling
is color coordinated.
The DATA SELECT key is used to display all trend-
ed Data Points simultaneously or select a single Data
Point for display.
The parameters are sampled at the selected Data Col-
lection Interval and plotted using 450 data points across
the X-Axis. If the actual value of the sampled param-
eter is less than the Y-Axis label minimum for that
parameter, the value will be plotted at the minimum
JOHNSON CONTROLS
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION

TREND SCREEN

value. Similarly, if the actual value is greater than the
Y-Axis label maximum for that parameter, the value
will be plotted at the maximum value.
There are three types of charts that can be created: One
Screen, Continuous or Triggered. When plotting reaches
the end of the X-Axis, if one screen is selected, trending
stops and data is frozen. If continuous is selected, the old-
est data is dropped from the left-hand side of the graph at
the next collection interval. Thereafter, the oldest data is
dropped from the left hand-side of the graph at each data
collection interval. If triggered is selected, data collection
can be set to start or stop based upon the selected Trigger
Action (start or stop). If start is selected, data collection
will not begin until the triggers have been satisfied and
any selected trigger delay has elapsed. Data collection
will stop at the completion of one screen of data as with
the one screen. If stop is selected, data collection will not
stop until the triggers have been satisfied and any selected
trigger delay has elapsed.
If a power failure occurs while the trending is running,
the trending is stopped. Upon restoration of power,
the last screen of data that was collected will be dis-
played on the TREND Screen. The START key must
be pressed to initiate a new TREND Screen.
00472VIP
155