FIGURE 47 - PRINTER SCREEN

OVERVIEW
This screen allows definition of the necessary commu-
nications parameters for the printer. Refer to SECTION
4 - PRINTING of this manual for details of the printer
connections and setup.
DISPLAY ONLY
Time Remaining Until Next Print
Displays the time until the next print log will occur, if
the function is enabled.
For fields requiring access level of SER-
VICE. Service Technicians refer to the
OptiView Control Center - Service Instruc-
tions (Form 160.76-M1) for operation
instructions and explanation of all pro-
grammable setpoints and displayed values.
PROGRAMMABLE
Log Start Time
Access Level Required: OPERATOR
Set the time at which scheduled print logs will begin.
JOHNSON CONTROLS
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION

PRINTER SCREEN

Output Interval
Access Level Required: OPERATOR
Define the interval at which log printing will occur.
Automatic Printer Logging (Enabled /
Disabled)
Access Level Required: OPERATOR
Enable the printer to begin printing status reports be-
ginning at the programmed start time and recurring at
the interval defined above.
Printer Type
Access Level Required: SERVICE
Define the printer type connected to the chiller system.
ACC Auto Map Print (Enabled / Disabled)
Access Level Required: SERVICE
Only available if the chiller system utilizes a Variable
Speed Drive motor controller. When a surge point is
mapped, a short report of system parameters is printed.
When this function is active, all other printing capabil-
ity is disabled.