FORM 160.76-O2
issue date: 6/15/2015
The Vibration Baseline values from which the Vibra-
tion Shutdown and Warning thresholds are derived,
are displayed on the MOTOR DETAILS Screen. The
thresholds are calculated from the Baseline values as
follows: (NOTE: if the calculated value exceeds the
minimum and maximum limits of the Shutdown (2.0 to
30.0) or Warning (1.0 to 15.0) threshold, the threshold
is set to the respective upper or lower limit).
• Shaft End High Vibration Warning - Shaft End
Vibration Baseline X2
• Shaft End High Vibration Warning Default - Shaft
End Vibration Baseline X2
• Opposite Shaft End High Vibration Warning -
Opposite End Vibration Baseline X2
• Opposite Shaft End High Vibration Warning
Default - Opposite End Vibration Baseline X2
• Shaft End High Vibration Shutdown - Shaft End
Vibration Baseline X3
• Shaft End High Vibration Shutdown Default -
Shaft End Vibration Baseline X3
• Opposite Shaft End High Vibration Shutdown -
Opposite Shaft End Vibration Baseline X3
• Opposite Shaft End High Vibration Shutdown
Default - Opposite Shaft End Vibration Baseline
X3
If no baseline values are entered, by either the auto
baseline routine or manual entry, the message WARN-
ING – MOTOR – BEARING VIBRATION BASE-
LINE NOT SET is displayed and the baseline values
JOHNSON CONTROLS
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
are set to X.X while this message is displayed. When
the Motor Vibration Protection Setpoint is set to Dis-
abled, no baseline vibration values are displayed and
the heading, text and data boxes do not appear.
Vibration Gain
Access Level Required: ADMIN
Only shown when access level is ADMIN and Motor
Vibration Protection Setpoint on MOTOR DETAILS
Screen is not set to Disabled. Allows a Service Techni-
cian to enter values for vibration Input Gain [1:1, 11:1,
21:1 (default)].
Bearing Setup
Access Level Required: SERVICE
Not shown when Bearing Temperature Protection
Setpoint on MOTOR DETAILS Screen is set to Dis-
abled. Allows a Service Technician to enter values for
High Bearing Temperature Shutdown (149 to 212°F;
default 203) and WARNING (140 to 194°F; default
194) thresholds.
NAVIGATION
Home
Access Level Required: SERVICE
Returns user to HOME Screen.
Motor Details
Access Level Required: SERVICE
Returns user to MOTOR DETAILS Screen.
2
117