FORM 160.76-O2
issue date: 6/15/2015

FIGURE 35 - SURGE MAP SCREEN - TABLE VIEW

OVERVIEW
The surge map can be shown in either Table (default) or
List view as selected with the MAP VIEW key. Shown
above is the Table View.
In this view, a table is used to graphically represent the
surge map in the view window. The X-Axis is Delta
P/P, the Y-Axis is Pre-rotation Vanes position and each
drive frequency point in the surge map is represented
by an "X". To view the details of any mapped point,
position the green box (□) over the desired "X" using
the keypad arrow keys (▲▼◄►). The drive Output
Frequency, Pre-rotation Vanes Position and Delta P/P
of the selected point is displayed at the bottom of the
screen under Selected. The default position for the
green box is in the upper left corner of the view win-
dow. Once moved, it will remain at the last position.
The Present Operating conditions are indicated with an
"*" (as shown above) and are detailed at the bottom
of the screen under Present. If the present condition is
the same as a mapped point, the "*" will be replaced
by an "O".
Use the pan Left, Pan Right, Pan Up and Pan Down to
pan the screen view.
JOHNSON CONTROLS

SURGE MAP SCREEN - TABLE VIEW

SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
LD19468
This screen is applicable to Variable Speed Drives
(VSD) and Medium Voltage Variable Speed Drives
(MV VSD.
Requires a login access level of SERVICE.
Service Technicians refer to the OptiView
Control Center - Service Instructions
(Form 160.76-M1) for operation instruc-
tions and explanation of all programmable
setpoints and displayed values.
DISPLAY ONLY
Mapping Inhibited (LED)
Illuminates while the Microboard ACC function is not
permitted to map points or reduce speed due to un-
stable Leaving Chilled Liquid Temperature, manual
speed control, current limit in effect (chiller FLA only)
or during Soft Shutdown otherwise, it is extinguished.
ACC Surge Detected (LED)
Illuminates momentarily when a surge is detected by
the ACC function in the Microboard, while the drive is
running at less than maximum frequency.