Installing/mounting
4.7 Installing the optional modules
4.7.2

Position feedback module

Function
● The optional position feedback module indicates the current position as a two-wire signal
● The current position is indicated only after successful initialization.
● Operational faults are signaled by a fault current of 3.6 mA.
Device features
Figure 4-11
The position feedback module is:
● Single channel
● Potentially separated from the basic device.
Requirements
You are familiar with the general procedure described in the section "General information about
the installation of option modules (Page 54)".
Procedure
1. Slide the position feedback module up to the endstop in the lower bay of the rack.
2. Connect the module to the basic electronics. For this purpose, use the 6-pin flat ribbon
62
with the travel range I
y
from the basic device.
Position feedback module
cable provided.
= 4 to 20 mA. The position feedback module is electrically isolated
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB