Installing/mounting

4.7 Installing the optional modules

The aforementioned measures are not adequate in some applications. For example,
continuous and strong vibrations, high or too low ambient temperatures and nuclear radiation.
The position detection system and the controller unit are mounted separately for these
applications. A universal component is available for this purpose. It is suitable for part-turn and
linear actuators. You will require the following:
● An external position detection system with the article number C73451-A430-D78
● Or an NCS sensor for contact-free position detection 6DR4004-6N.../-8N...
● A positioner
● An EMC filter module with the article number C73451-A430–D23 is provided in a set along
The EMC filter module is used for the controller unit whenever an external position detection
system is used instead of the internal position sensor. An external position detection system
is, for example, a potentiometer with a 10 kΩ resistance or an NCS sensor.
4.7
Installing the optional modules
4.7.1

General information about the installation of option modules

4.7.1.1

Unsuitable device for the hazardous area

Unsuitable device for the hazardous area
Danger of explosion.
● Only use equipment that is approved for use in the intended hazardous area and labelled
4.7.1.2

Installing optional modules in the standard and intrinsically safe version

Introduction
The following option modules are available for the positioner in the standard and intrinsically
safe version:
● Position feedback module
● Alarm module
● SIA module
54
comprising a positioner enclosure with integrated friction clutch, built-in potentiometer as
well as various blanking plugs and seals.