Alarm, fault and system messages
11.2 Diagnostics
11.2.4.29

Diagnostic value '46.STORE - Save maintenance data'

Purpose:
11.2.4.30

Diagnostic value '47.PRUP - Prediction UP' / '48.PRDN - Prediction DOWN'

Display range:
Purpose:
Factory setting:
11.2.4.31
Diagnostic value '49.WT00' ... '56.WT95' - Number of operating hours in the travel range

WT00 to WT95

Display range:
Purpose:
266
The minimum and maximum temperatures within the enclosure are
constantly determined and saved as with a slave pointer. This value
can only be reset in the factory. In order to switch over the temper‐
ature display between °C and °F, press the
seconds in order to initiate a save function. The values of the diag‐
nostics parameters Diagnostic value '8.WAY - Determined travel'
(Page 256) to Diagnostic value '11.LEAK - Leakage test'
(Page 257) and Diagnostic value '21.P0 - Potentiometer value of
lower endstop (0%)' / '22.P100 - Potentiometer value of upper end‐
stop (100%)' (Page 261) to Diagnostic value '28.SSUP - Slow step
zone UP' / '29.SSDN - Slow step zone DOWN' (Page 263) are saved
in the non-volatile memory as 'data of last maintenance'. This diag‐
nostics data contains selected values whose changes can give in‐
formation about mechanical wear and tear of the valve.
This function is normally operated through the PDM, menu com‐
mand 'Diagnostics-> Save maintenance information'. The data of
the last maintenance operation can be compared with the current
data using SIMATIC PDM.
1 ... 40
This value specifies the prediction of the controller for the up (PRUP)
and down (PRDN) movements.
For more information, refer also to the section Optimization of con‐
troller data (Page 110).
1
0 ... 4.29E9
When the positioner is in "Automatic" mode, statistics are continu‐
ously maintained regarding the duration for which a valve or a flap
is operated in a particular section of the travel range. The entire
travel range is divided into 8 sections from 0 to 100 %. The positioner
records the current position continuously and increments the run‐
time meter assigned to the corresponding travel range every hour.
This helps in drawing conclusions about the past operating condi‐
tions and especially in assessing the control properties of the control
loop and the entire control valve.
key for at least 5
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB