Parameter assignment
9.3 Description of parameters
O1.LIMIT - Limit for number of changes in direction
Adjustment range:
Purpose:
Factory setting:
O2.FACT1 - Factor 1
Adjustment range:
Purpose:
Factory setting:
O3.FACT2 - Factor 2
Adjustment range:
Purpose:
Factory setting:
O4.FACT3 - Factor 3
Adjustment range:
Purpose:
Factory setting:
194
1 ... 1.00E8
Use this sub-parameter to set the base limit for the changes of direction of the
actuator. Set the base limit in a range from '1' to '1.00E8'.
1.00E6
0.1 ... 40.0
Use this sub-parameter to set the factor for formation of threshold 1. Set the factor
in a range from '0.1' to '40.0'. The threshold is the product of 'O1.LIMIT' and
'O2.FACT1'.
The threshold 1 message is displayed when threshold 1 is exceeded. The process
to activate and display this message is described in the 'XDIAG' parameter.
1.0
0.1 ... 40.0
Use this sub-parameter to set the factor for formation of threshold 1. Set the factor
in a range from '0.1' to '40.0'. The threshold is the product of 'O1.LIMIT' and
'O3.FACT2'.
The threshold 1 message is displayed when threshold 1 is exceeded. The process
to activate and display this message is described in the 'XDIAG' parameter.
2.0
0.1 ... 40.0
Use this sub-parameter to set the factor for formation of threshold 1. Set the factor
in a range from '0.1' to '40.0'. The threshold is the product of 'O1.LIMIT' and
'O4.FACT3'.
The threshold 1 message is displayed when threshold 1 is exceeded. The process
to activate and display this message is described in the 'XDIAG' parameter.
5.0
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB