A3.STRKH - Stroke height
Adjustment range:
Purpose:
Factory setting:
A4.STRKD - Stroke direction
Possible settings:
Purpose:
Formula (uP):
Formula (do):
Formula (uP do)
Factory setting:
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
0.1 ... 100.0
Use this sub-parameter to define the stroke height of the partial
stroke test in percent. Set the stroke height in a range from '0.1' to
'100.0'.
10.0
● uP
● do
● uP do
Use this sub-parameter to set the stroke direction of the partial
stroke test.
uP: Actuator only moves upward
● The actuator moves from its start position to the upper target
position.
● After reaching the upper target position, the actuator moves back
to the start position.
Upper target position = Start position (A1.STPOS) ± Start tolerance
(A2.STTOL) + Stroke height (A3.STRKH)
do: Actuator only moves downward
● The actuator moves from its start position to the lower target
position.
● After reaching the lower target position, the actuator moves back
to the start position.
Lower target position = Start position (A1.STPOS) ± Start tolerance
(A2.STTOL) + Stroke height (A3.STRKH)
uP do: Actuator moves up and down
● The actuator first moves from its start position to the upper target
position.
● It then moves from the upper target position to the lower target
position.
● After reaching the lower target position, the actuator moves back
to the start position.
Target position = Start position (A1.STPOS) ± Start tolerance
(A2.STTOL) + Stroke height (A3.STRKH)
do
Parameter assignment
9.3 Description of parameters
175