Commissioning
7.5 Commissioning linear actuators
5. Call the "4.INITA" parameter. To do this, briefly press the
6. Start the initialization process. To do this, press the
7. The following display indicates that the automatic initialization is complete:
Aborting the automatic initialization process
1. Press the
2. Exit the "Configuration" mode. To do this, press the
See also
Sequence of automatic initialization (Page 116)
126
following:
the display shows the following:
The positioner runs through five initialization steps during the automatic initialization
process. Displays for the initialization steps from "RUN 1" to "RUN 5" are shown in the lower
line on the display. The initialization process depends on the actuator used, and takes up
to 15 minutes.
button. The display shows the following:
The positioner is in the "Configuration" mode.
The software status is displayed.
After releasing the
initialized.
button, the positioner is in "P manual mode". The positioner is not
button. The display shows the
button for at least 5 seconds until
button for at least 5 seconds.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB