SolarEdge StorEdge Installation Manual page 81

For smart energy management using lg chem batteries
Hide thumbs Also See for StorEdge:
Table of Contents

Advertisement

Creating an RS485 Bus Connection
 6.  For creating an RS485 bus - connect all B, A and G pins in all inverters. The following figure shows this 
connection schema:
 
NOTE
Do not cross-connect B, A and G wires.
 7.  Tighten the terminal block screws.  
 8.  Check that the wires are fully inserted and cannot be pulled out easily. 
 9.  Push the RS485 terminal block firmly all the way into the connector on the right side of the 
communication board. 
 10.  Terminate the first and last SolarEdge device  in the chain by switching a termination DIP-switch inside 
the inverter to ON (move the left switch up). The switch is located on the communication board and 
is marked SW7. 
NOTE
Only the first and last SolarEdge devices in the chain should be terminated. The other inverters in
the chain should have the termination switch OFF (down position).
 11.  If not using surge protection, connect the grounding wire to the first inverter in the RS485 chain; 
make sure the grounding wire is not in contact with other wires. For inverters with a StorEdge 
Connection Unit, connect the grounding wire to the grounding bus-bar in the StorEdge Connection 
Unit.
78
Figure 43: Connecting the inverters in a chain
Figure 44: RS485 termination switch
StorEdge Inverter Installation Guide MAN-01-00390-1.1
 