Creating an RS485 Bus Connection

 7. For the switch/router side, use a pre-crimped cable or use a crimper to prepare an RJ45 
communication connector: Insert the eight wires into the RJ45 connector in the same order as above 
(Figure 39).
 8. Connect the cable RJ45 connector to the RJ45 port of the Ethernet switch or router.
You can connect more than one inverter to the same switch/router or to different switches/routers,
as needed. Each inverter sends its monitored data independently to the   m onitoring platform.
 9. The inverter is configured by default to LAN. If   r econfiguration is required:
 a. Make sure the ON/OFF switch is OFF.
 b. Turn ON the AC to the inverter by turning ON the circuit breaker on the main distribution panel.
 c. Use the internal user buttons to configure the connection, as described in Communication on
page 57.
NOTE
If your network has a firewall, you may need to configure it to enable the connection to the
following address:
Destination Address: prod.solaredge.com
TCP Port: 22222, 22221, or 80 (for incoming and outgoing data)
 10. Verify the connection, as described in Verifying the Connection on page 79.
Creating an RS485 Bus Connection
The RS485 option enables creating a bus of connected inverters, consisting of up to 31 slave inverters and 
1 master inverter. Using this option, inverters are connected to each other in a bus (chain), via their 
RS485 connectors. The first and last inverters in the chain must be terminated as described on page 78.
RS485 wiring specifications:
Cable type: Min. 3-wire shielded twisted pair (a shielded Ethernet cable (Cat5/5E STP) may be used)
Wire cross-section area: 0.2- 1 mm²/ 24-18 AWG (a CAT5 cable may be used)
Maximum nodes: 32
Maximum distance between first and last devices: 1 km /3300 ft. 
NOTE
If using a cable longer than 10 m/33 ft in areas where there is a risk of induced
voltage surges by lightning, it is recommend to use external surge protection
devices. For details refer to:
https://www.solaredge.com/sites/default/files/lightning_surge_protection.pdf.
If grounded metal conduit are used for routing the communication wires, a lightning
protection device is not required.
If not using surge protection, connect the grounding wire to the first inverter in the RS485 chain;
make sure the grounding wire is not in contact with other wires. For inverters with a StorEdge
Connection Unit, connect the grounding wire to the grounding bus-bar in the StorEdge Connection
Unit.
76
StorEdge Inverter Installation Guide MAN-01-00390-1.1