Creating an Ethernet (LAN) Connection
Creating an Ethernet (LAN) Connection
This communication option enables using an Ethernet connection to connect the inverter to the
monitoring platform through a LAN.
Ethernet cable specifications:
Cable type – a shielded Ethernet cable (Cat5/5E STP) may be used
Maximum distance between the inverter and the router – 100 m/ 330 ft.
NOTE
If using a cable longer than 10 m / 33 ft in areas where there is a risk of induced
voltage surges by lightning, it is recommend to use external surge protection
devices.
For details refer to:
protection.pdf.
To connect the Ethernet cable:
1. Remove the inverter cover .
2. Open the communication gland #1.
CAUTION!
The gland includes a rubber waterproof fitting, which should be used to ensure proper sealing.
3. Remove the plastic seal from one of the large opening .
4. Remove the rubber fitting from the gland and insert the CAT5/6 cable through the gland and through
the gland opening in the inverter .
5. Push the cable into the cut opening of the rubber fitting.
74
http://www.solaredge.com/files/pdfs/lightning_surge_
Figure 37: Example of Ethernet connection
Figure 38: Rubber fitting
StorEdge Inverter Installation Guide MAN-01-00390-1.1