System Warnings

Warnings are displayed in the initial status screen with the format: <Warning X>. For example:
V a c [ V ]
1 . 0
P _ O K :
X X X / Y Y Y
W a r n i n g
The warning is a status screen. To view the warning description, press the LCD button. 
The following is a list of system warnings:
Warning #
CPU
CPU
v3.18xx and
v3.19xx and
before
later
8x66 - 8x69
1-4, 6-7
8x6A - 8x6F
5
8
2x111
StorEdge Inverter Installation Guide MAN-01-00390-1.1
LCD Message
Power overload
OFF and ON to resume
Backup init over voltage
Internal CB down
V d c [ V ]
P a c [ W ]
0 . 5
0 . 0
< S _ O K >
8
O N
LCD text
Fan # Failure
Turn Switch Off to Configure
Connection Unit Low 9V Battery
Appendix A: Troubleshooting
Cause and Troubleshooting
Inverter output is overloaded or output current
is higher than battery max allowed output. The
inverter tried to restart 3 times.
External voltage source on backed-up
o
loads when operating in Backup mode.
Disconnect all external voltage sources on
backed-up loads.
Inverter internal error. Contact SolarEdge
o
support.
Make sure that the loads do not consume
higher current than the inverter max output
current. Open the inverter StorEdge
Connection Unit and switch the main circuit
breaker to the ON position.
Comments and
troubleshooting
Clean or replace the fan
Appears when trying to access the Setup
menus during production
Replace the 9V battery in the StorEdge
Connection Unit. Refer to 9V Battery
Replacement on page 104.