Storedge Connection Unit Leds - SolarEdge StorEdge Installation Manual

For smart energy management using lg chem batteries
Hide thumbs Also See for StorEdge:
Table of Contents

Advertisement

StorEdge Connection Unit LEDs

There are three LEDs on the lower board of the StorEdge Connection Unit, near the DIP switches: 
In normal operation, the middle and bottom LEDs indicate auxiliary voltages (13V from DC/DC, 5V and 
 
3.3V) and should always be   l it.  
The top LED should be lit when the inverter DC voltage is at least 200 Vdc (check when both inverter 
 
ON/OFF switch and StorEdge Connection Unit switch are ON). You can check the status screen for 
the Vdc value.
If all LEDs are OFF: 
 
Check that AC voltage exists in the inverter
 
o
Check that the communication cable between the StorEdge Connection Unit and the digital 
 
o
board is properly connected.
If the top LED is ON, and middle and bottom LEDs are off - an internal failure has occurred. Contact 
 
SolarEdge support.
StorEdge Inverter Installation Guide MAN-01-00390-1.1
Figure 47: StorEdge Connection Unit LEDs
Appendix A: Troubleshooting
97