SolarEdge SE50K Installation Manual page 64

Extended power commercial inverter
Hide thumbs Also See for SE50K:
Table of Contents

Advertisement

 5.  Loosen the screws of pins A(+), B(-), and G in either the 'Out' or 'In' RS485 terminal block.
 6.  Insert the wire ends into the G, A and B pins shown above. Use one terminal block for the previous 
inverter in the bus and the other terminal block for the next inverter in the bus, as shown in Figure 34. 
You can use any color wire for each of the A, B and G connections, as long as the same color wire is 
used for all A pins, the same color for all B pins and the same color for all G pins.
 7.  Connect all B, A and G pins in all inverters. The following figure shows this connection schema:
 8.  Tighten the terminal blocks screws.  
 9.  Check that the wires are fully inserted and cannot be pulled out easily. 
 10.  Push the RS485 terminal blocks firmly all the way into the connectors on the communication board, 
see Figure 32.
 11.  Terminate the first and last inverters on the bus by moving the termination switch to ON (left 
position). The other inverters on the bus should have the termination switch OFF (right position).
Extended Power Commercial Inverter Installation Guide MAN-01-00402-1.0
Figure 33: RS485 terminal block wire connections
Figure 34: Connecting the inverters on a bus
Chapter 6: Setting Up Communication
63