 f.  Select the following to configure the connection:
 
Server è LAN
l
 
LAN è DHCP è Enable
l
DHCP
Static IP Configuration
Modbus TCP port
 13.  Verify the connection, as described in Verifying the Connection  on page 65.
NOTE
The system automatically establishes communication with the monitoring platform as it is
configured to LAN by default.
 
NOTE
If your network has a firewall, you may need to configure it to enable the connection to the
following address:
Destination Address: prod.solaredge.com
l
Modbus TCP Port: 22222 (for incoming and outgoing data)
l
 

Creating an RS485 Bus Connection

The RS485 option enables creating a bus of connected inverters, consisting of up to 31 slave inverters and 
1 master inverter. Using this option, inverters are connected to each other in a bus (chain) via their RS485 
connectors, thus allowing to connect only the master inverter to the monitoring platform. The first and 
last inverters in the chain must be terminated as described in RS485 Bus Configuration on page 64
RS485 wiring specifications:
 
Cable type: Min. 3-wire shielded twisted pair (a shielded Ethernet cable (Cat5/5E STP) may be used)
l
 
Wire cross-section : 0.2- 1 mm²/ 24-18 AWG 
l
 
Maximum distance between first and last devices: 1 km /3300 ft. 
l
The following sections describe how to physically connect the RS485 bus and how to configure the bus.
 
Extended Power Commercial Inverter Installation Guide MAN-01-00402-1.0