NOTE
If using a cable longer than 10 m / 33 ft in areas where there is a risk of induced
voltage surges by lightning, it is recommend to use external surge protection
devices.
For details refer to:
protection.pdf.
To connect the Ethernet cable:
1. Open the communication gland.
CAUTION!
The gland includes a rubber waterproof fitting, which should be used to ensure proper sealing.
2. Remove the rubber fitting from the gland and insert the CAT5/6 cable through the gland and through
the gland opening in the Connection Unit .
3. Remove the plastic seal from the large opening that has a cut in the rubber fitting.
4. Push the cable into the cut opening of the rubber fitting.
CAT5/5E STP cables have eight wires (four twisted pairs), as shown in the diagram below. Wire colors may
differ from one cable to another. You can use either wiring standard, as long as both sides of the cable
have the same pin-out and color-coding.
Extended Power Commercial Inverter Installation Guide MAN-01-00402-1.0
http://www.solaredge.com/files/pdfs/lightning_surge_
Figure 28: Example of Ethernet connection
Figure 29: Communication gland and rubber fitting
Chapter 6: Setting Up Communication