Main Inverter Status - SolarEdge SE50K Installation Manual

Extended power commercial inverter
Hide thumbs Also See for SE50K:
Table of Contents

Advertisement

Main Inverter Status

SN 07318000C
Power
100 kW
P_OK: 138 of 141
Optimizers Connected
Status
Production
CosPhi
1.00
Voltage
850 Vdc
Switch Off. Production disabled
Commissioning
 
Inverter: The inverter serial number
l
 
Power: The AC output power
l
 
Voltage (Vac): The AC output voltage
l
 
Frequency: The AC output frequency
l
 
P_OK: xxx of yyy: There is a connection to the power optimizers and at least one power optimizer is 
l
sending monitoring data. XXX is the number of power optimizers for which telemetries have been 
received in the last two hours. YYY is the number of paired power optimizers identified during the 
most recent pairing process. If XXX and YYY are not equal, there may be a problem in one or more 
power optimizers.
 
S_OK: The connection to the SolarEdge monitoring platform is successful (appears only if the inverter 
l
is connected to the monitoring platform).
 
Status: The inverter operation status: Off, Not Paired, Night Mode, Error, Pairing, or Production
l
 
Switch: Indicates the position of the inverter ON/OFF/P switch: On, Off, or P position.
l
 
CosPhi: Indicates the ratio between active and reactive power.A negative value indicates a lagging 
l
CosPhi.
For more information, refer to the Power Control Application Note, available on the 
SolarEdge website at http://www.solaredge.com/files/pdfs/application_note_
power_control_configuration.pdf.
 
Limit: The inverter maximum output power
l
 
Country: The selected country and grid setting
l
 
Voltage (Vdc): The DC input voltage
l
 
Temp (°C or °F): The inverter heat sink temperature
l
Extended Power Commercial Inverter Installation Guide MAN-01-00402-1.0
Chapter 5: Activating, Commissioning and Configuring the System Using SolarEdge
Status
Inverter
Voltage
Frequency
277 Vac
60.9 Hz
S_OK
Server Connected
Switch
OFF
Limit
Country
No Limit
Netherlands
Temp
Fan
20 C
OK