Selecting a Residual Current Device (RCD)

IMPORTANT SAFETY FEATURE
 
All SolarEdge inverters incorporate a certified internal Residual Current Device (RCD) in order to 
protect against possible electrocution and fire hazard in case of a malfunction in the PV array, 
cables or inverter. There are 2 trip thresholds for the RCD as required for certification (DIN VDE 
0126-1-1). The default value for electrocution protection is 30 mA per unit , and for slow rising 
current is 300 mA per unit.
If an external RCD is required by local regulations, check which type of RCD is required for the relevant 
electric code. Install the residual-current device (RCD) in accordance with the applicable local standards 
and directives. SolarEdge recommends using a type A RCD. When required by local regulations, the use of 
an RCD type B is permitted.
Use at least 600mA RCD for a 2 unit inverter and at least 900mA RCD for a 3 unit inverter.
NOTE
For multiple inverters, an RCD per inverter is required.
You have completed installing the system, proceed to the next chapter to activate and commission it, 
then to Setting Up Communication     on page 52, to   s et up required communication options and to set up 
master slave configurations, if required.