Configuration DIP Switches
Modbus
BACnet
DIP
Position
1
Modbus
BACnet
2-4
A
Off
Off
Off
Off
On
On
On
On
5
Parity Even
Parity None
6
Non-Metric
Metric
7
Not used
8
Not used
10
A B
ON
2 3 4 5 6 7 8
1
Baud
Rate
Setting
Modbus protocol in use.
BACnet protocol in use.
B
C
Serial line baud rate
Off
Off
Automatic (default)
Off
On
4800
On
Off
9600
On
On
19200
Off
Off
38400
Off
On
57600
On
Off
76800
On
On
115200
Parity even (8E1).
Only affects Modbus protocol.
Parity none (8N2).
Only affects Modbus protocol.
Use non-metric units (°F).
Only affects display and service port.
Use metric units (°C).
Only affects display and service port.
Parity Even
Non-Metric
C
Metric
Parity None