Appendix B: Replacing and Adding System Components

Appendix B: Replacing and Adding System
Components
NOTE
If you are permanently disassembling the installation or part of it, make sure to use the disposal
methods dictated by local regulations.
CAUTION!
Do not remove the six screws on the DC conduit metal panel as it may
harm the inverter sealing and void the warranty.
Ces vis ne doivent pas être retirées. Les enlever est susceptible
d'endommager l'étanchéité de l'onduleur et annuler la validité de la
garantie.

Replacing an Inverter

 1. Turn OFF the inverter ON/OFF switch, and wait until the LCD indicates that the DC voltage is safe 
(<50V), or wait five minutes before continuing to the next step.
WARNING!
If you cannot see the inverter panel, or if a malfunction is indicated on the LCD panel, wait five
minutes for the input capacitors of the inverter to discharge.
Si vous ne pouvez pas voir l'écran de l'onduleur ou si un dysfonctionnement est indiqué sur
l'écran LCD, attendez cinq minutes pour que les condensateurs d'entrée de l'onduleur soient
déchargés.
 2. Turn OFF the StorEdge Connection Unit.
 3. Open the StorEdge Connection Unit cover.
 4. Turn the Bypass switch inside the StorEdge Connection Unit to position 2, in order to maintain power
to the backed-up loads.
 5. Open the inverter cover as described in Removing the Inverter Cover on page 39.
 6. Disconnect the DC and AC wires from the inverter. Open the DC and AC wires   f errite beads and set
them aside.
 7. Disconnect the cable connecting the inverter digital board to the StorEdge Connection Unit.
 8. Unscrew the two conduit nuts in the inverter securing the StorEdge Connection Unit to the inverter.
 9. Remove the screws securing the inverter to the mounting bracket and remove the inverter from the 
mounting bracket.
NOTE
If you remove the old inverter and do not immediately install a new one, then:
Lock the StorEdge Connection Unit in the OFF position using a lock on the switch.
o
Use insulation tape to isolate each of the AC and DC wires.
o
Seal the open conduits using duct tape.
o
 10. Place the new inverter on the mounting bracket; insert the screws securing the inverter to the 
mounting bracket.
 11. Screw the two conduit nuts in the inverter securing the StorEdge Connection Unit to the inverter.
 12. Connect the DC and AC wires to the inverter.