Status Registers; Table 58 Modbus Status Registers (Read-Only); Table 59 Modbus Device Status Bits; B.4.2 Status Registers - Vaisala MHT410 User Manual

Vaisala moisture, hydrogen and temperature transmitter for transformer oil
Table of Contents

Advertisement

Register
Address
Number
(Hexadecimal)
259
0102
hex
260
0103
hex
261
0104
hex
264
0107
hex
265
0108
hex
266
0109
hex
267
010A
hex
268
010B
hex
269
010C
hex
270
010D
hex
PDU address
Actual address bytes used in a Modbus Protocol Data Unit
LSW
Least Significant Word (bits 15...0)
MSW
Most Significant Word (bits 31...16)
16-bit integer
Numeric value in range -32768...32767
32-bit float
Floating point number encoded according to IEEE 754
B.4.2 Status Registers
Table 58 Modbus Status Registers (Read-only)
Register Number
513
Table 59 Modbus Device Status Bits
Output
Output Name
(bit mask)
0
Status OK
1
Critical Error active
2
Error active
Register Description
H
, Daily ROC
2
H
, Weekly ROC
2
H
, Monthly ROC
2
Oil moisture, relative
saturation
Oil moisture, current
Oil moisture, 24h
average
Oil moisture, Daily ROC
Oil moisture, Weekly
ROC
Oil moisture, Monthly
ROC
Oil temperature
Address (Hexadecimal)
02 00
hex
Notes
Maintenance needed.
Device may recover automatically.
Appendix B – Modbus Reference
Data Format
16-bit integer
16-bit integer
16-bit integer
16-bit integer
16-bit integer
16-bit integer
16-bit integer
16-bit integer
16-bit integer
16-bit integer
Register Description
Device status bits
Unit
ppm
(in oil)
v
ppm
(in oil)
v
ppm
(in oil)
v
%RS*10
ppm
*10
w
ppm
*10
w
ppm
*10
w
ppm
*10
w
ppm
*10
w
°C *10
Data Format
16-bit integer
107

Advertisement

Table of Contents
loading

Table of Contents