M12 Connector In The Basic Device; M12 Connector For Connection Of The Outputs Of The Alarm Module 6Dr4004-6A / -8A (-Z D55) - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

View of the mating side pole pattern
5.2.3.1

M12 connector in the basic device

You have a positioner 6DR50..-0.R.. or 6DR50..-0.S.. In this version of the positioner, the
current input I
Table 5-1
Current input terminal
6 (+)
Shield support of housing
7 and 8 (-)
5.2.3.2
M12 connector for connection of the outputs of the alarm module 6DR4004-6A / -8A (-Z
D55)
You have a positioner with order suffix -Z order code D55. In this version of the positioner, the
M12 connector is used to electrically connect the current output of the position feedback
module.
Table 5-2
Alarm output terminal
41 (+)
52 (-)
42 (-)
51 (+)
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
4 to 20 mA of the basic electronics is connected via the M12 connector.
W
Assignment diagram
Assignment diagram
5.2 Electrical wiring
Pole designation Wire color of M12
connector
1
Brown
4
Black
3
Blue
2
White
Pole designation
1 - Brown
4 - Black
3 - Blue
Pole designation
1 - Brown
4 - Black
3 - Blue
2 - White
Connection