Installing The Internal Ncs Module 6Dr4004-5L/-5Le - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

4.6.6

Installing the internal NCS module 6DR4004-5L/-5LE

Function
Wear-free, contact-free position detection
Device features
(B) Internal NCS module 6DR4004-5L.
(C) Insulating cover, yellow
(D) Ribbon cable of the internal NCS mod‐
Figure 4-15
Requirement
● The slot required for the internal NCS (iNCS) module in the rack is free. The following option
modules use the same slot in the rack:
– Alarm module
– SIA module
– Mechanical limit switch module
– Internal NCS module
● The positioner is mounted, or is to be mounted, directly on the valve using the positioner
shaft.
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
ule
Installing the internal NCS module
(F) Adjustment wheel for the magnet clamp
(G) Adjustment wheel for the friction clutch (without
function)
Installing/mounting
4.6 Installing option modules
67