Installing/mounting
4.2 Mounting the linear actuator
1. Install the clamping pieces
socket cap screws
2. Slide the pick-up bracket
Figure 4-1
3. Set the necessary length.
4. Tighten the screws
5. Fix the pre-installed carrier pin
Figure 4-2
6. Set the stroke value. Use the stroke value specified on the nameplate of the actuator for
this purpose. If none of the values on the lever scale matches the stroke value of the
actuator, select the next higher value on the scale. Position the pin center
corresponding value of the scale. If you need the value of actuator travel after initialization
in mm: ensure that the configured stroke value matches the value of the "3.YWAY"
parameter.
38
for this purpose.
Pick-up bracket
so that you can still shift the pick-up bracket
and hexagon nut
for this purpose.
Lever with carrier pin
on the actuator spindle. Use spring lock washers
into the milled recesses of the clamping pieces
to the lever
. Use the flat washer
Operating Instructions, 05/2017, A5E00074631-AC
and
.
.
, spring lock washer
on the
SIPART PS2 with and without HART