Siemens SIPART PS2 Operating Instructions Manual page 299

Electropneumatic positioner
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Construction
Weight
Material body
Number of channels, basic electronics:
Climate class
● Storage
● Transport
● Operation
Electrical data
Electrical connection
Current input I
W
● Rated signal range
● Current to maintain the auxiliary power
2-wire connection
● Current to maintain the auxiliary power
● Required load voltage U
● Static destruction limit
Technical specifications for the controller unit is available at Controller (Page 234).
Technical specifications for the position feedback module is available at Position feedback
module (Page 241).
Cable data (minimum requirements)
Cable length
Capacity wire / wire
Capacity wire / shield
Inductance
Copper resistance
Insulation conductance
Ambient temperature
Number of poles
● Cable to the control system (min/max)
● Cable to the positioner 6DR5910
Connection
● Cable to the control system (min/max)
● Cable to the positioner 6DR5910
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
(corresponds to Ω at 20 mA)
B
Positioner with remote control electronics
Approx. 1.8 kg
10" slide-in module, 2HM, aluminum
3
According to IEC/EN 60721-3
-25°C to 80°C, 75% at 25°C, without condensation
-25°C to 80°C, 75% at 25°C, without condensation
0°C to 50°C, 75% at 25°C, without condensation
9-pin Sub-D plug
15-pin Sub-D female connector
4 to 20 mA
≥ 3.6 mA
≥ 3.6 mA
6.4 V (= 320 Ω)
± 40 mA
≤ 130 m
≤ 150 nF/km
≤ 200 nF/km
≤ 1 mH/km
≤ 100 Ω/km
≥ 0.5 x 10
S/km
7
-30 ... +80 °C
4 or 9
8 or 15
9-pin Sub-D female connector
15-pin Sub-D male connector
F.2 19" slide-in module