Electrical Connection Of 19" Slide-In Module 4 To 20 Ma - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Positioner with remote control electronics
F.2 19" slide-in module
Notes on the individual connection points:
F.2.2.2

Electrical connection of 19" slide-in module 4 to 20 mA

Requirement
You have read sections Connection (Page 73) and Grounding concept 19" slide-in module 4
to 20 mA (Page 294).
296
The cable shield is not connected to the positioner 6DR5910.
The positioner 6DR5910 is connected via the mechanical assembly to Ground 2 , see
Installing/mounting (Page 33). Section Basic safety instructions (Page 73) describes
how to ground the enclosure.
Each field distributor is grounded. The cable shields in the field distributor are not
grounded. The cable shields are interconnected.
The cable shields on the 19" slide-in module are interconnected.
The 19" slide-in module is connected to Ground 1.
The cable shields on the control system are not connected to ground.
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC