Return Procedure - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Replacing the basic electronics with the "Fail in Place" function
When replacing the basic electronics for positioning controllers with the function "Fail in Place",
order suffix -Z F01, the parameters for the pneumatic type have to be set. The procedure is
described here.
Note
Possible movement of the actuator
While replacing the basic electronics, the actuator can unintentionally vent itself.
● Observe the procedure described below.
1. Switch off the supply air PZ.
2. Remove the enclosure cover of the positioner.
3. Replace the basic electronics as described in section "General information on installing
option modules (Page 51)".
4. Set the "'51.PNEUM' Pneumatics type (Page 164)" parameter from "Std" to "FIP".
5. Install the enclosure cover.
6. Switch on the supply air PZ again.
7. Initialize the positioner as described in section "Commissioning (Page 105)"
11.5

Return procedure

Enclose the bill of lading, return document and decontamination certificate in a clear plastic
pouch and attach it firmly to the outside of the packaging.
Required forms
● Delivery note
● Return document (http://www.siemens.com/processinstrumentation/returngoodsnote)
with the following information:
– Product (item description)
– Number of returned devices/replacement parts
– Reason for returning the item(s)
● Decontamination declaration (http://www.siemens.com/sc/declarationofdecontamination)
With this declaration you warrant "that the device/replacement part has been carefully
cleaned and is free of residues. The device/replacement part does not pose a hazard for
humans and the environment."
If the returned device/replacement part has come into contact with poisonous, corrosive,
flammable or water-contaminating substances, you must thoroughly clean and
decontaminate the device/replacement part before returning it in order to ensure that all
hollow areas are free from hazardous substances. Check the item after it has been cleaned.
Any devices/replacement parts returned without a decontamination declaration will be
cleaned at your expense before further processing.
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
Service and maintenance
11.5 Return procedure
229