Alarm, error, and system messages
10.3 Online diagnostics
10.3.2

Overview of online diagnostics

Online diagnostics means diagnostics during ongoing operation. During operation of the
positioner, a few important values and parameters are continually monitored. In configuration
mode, you can configure that monitoring so that the fault message output will be activated if,
for instance, a limit is exceeded.
Information about what events can activate the fault message output can be found in the table
in section "Overview of error codes (HART/PA) (Page 214)".
This section contains particular information about the following situations:
● Possible causes of the fault message.
● Events which activate the fault message output or alarm outputs.
● Settings of parameters needed for event monitoring.
● Cancelling an error message
When the fault message output is triggered in "Automatic" or "Manual" mode, the display shows
which fault triggered the message. The two digits on the lower left show the corresponding
error code. If multiple triggers occur at the same time, they are displayed one after the other
cyclically. The device status, including all fault messages, can be called up using command
"#48" over HART.
See also
'52.XDIAG' Activating for extended diagnostics (Page 166)
Extended diagnostics parameters A to P (Page 167)
10.3.3

XDIAG parameter

You can use the extended diagnostics parameters to display error messages in one, two or
three stages. In addition to the fault message output, alarm outputs 1 and 2 are then used. For
this purpose, set the "XDIAG" parameter as described in the following table:
Settings of XDIAG
OFF
On1
On2
On3
Possible settings of the 'XDIAG' parameter
216
Message due to
Extended diagnostics not activated
Fault message output for threshold 3 error message (maintenance alarm, single-stage)
Fault message output for threshold 3 error messages and alarm output 2 for threshold 2
error messages (maintenance demanded, two-stage)
Fault message output for threshold 3 error messages and alarm output 2 for threshold 2
error messages and alarm output 1 for threshold 1 error messages (maintenance required,
three-stage)
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC