Parameter assignment
9.4 Description of parameters
P1.TBASE - Time basis of average value generation
Possible settings:
Purpose:
Factory setting:
P2.STATE - Status of monitoring position average value
Possible settings:
Purpose:
Factory setting:
Note
Current average value of position
The respective current average value of position is displayed in the Diagnostic value '20.PAVG
- Average value of position' (Page 206). If no average value of position has been calculated,
'COMP' is displayed as the diagnostic value.
190
0.5h / 8h / 5d / 60d / 2.5y
Use this sub-parameter to set the time interval to calculate the aver‐
age value of position. The following values are available to define
the time intervals:
● 30 minutes
● 8 hours
● 5 days
● 60 days
● 2.5 years
After starting the calculation for average value of reference and ex‐
piry of the time interval, a position average over the interval period
is determined and compared with the average value of reference.
The test is then restarted.
0.5h
IdLE / rEF / ###.# / Strt
Use this sub-parameter to start the calculation for average value of
position. If an average value of reference has never been deter‐
mined, the parameter value is 'IdLE'.
Then start the calculation by pressing the
The value in the display changes from 'IdLE' to 'rEF'. The average
value of reference is calculated.
When the time interval expires, the calculated average value of ref‐
erence is shown on the display.
IdLE
button for 5 seconds.